Application Scenarios
Suitable for switching stations or distribution rooms adopting single busbar sectionalized scheme with dual power supply access.
Applicable to sites requiring high power supply reliability with dual power access and single busbar sectioning; two busbar sections operate in isolation. When one feeder loses voltage, the bus tie cubicle can supply power to the de-energized busbar and improve system power supply reliability.
Can be installed in distribution rooms and outdoor switch cabinets.
Main Parameters
| Rated Voltage | 12kV & 24kV |
| Rated Current | 630A & 1250A |
| Rated Short-circuit breaking Current | 20kA / 25kA |
| Dimension (W × D × H) | 12kV: 5470×800×1640 24kV: 6640 ×850×1890 Dimensions without secondary top box Note: Take 630A product as an example |
| Design life | 40 years |
| Optional Accessories | • Surge arresters • EKL4 short-circuit & earth fault indicator • Electrical interlocks and key interlocks to prevent parallel operation of two power sources • Tripping coil 1: AC230V / DC48V / DC110V • Tripping coil 2: Under-voltage release coil, AC230V |
Let's get in touch!
No matter which stage your project is at, our professional team of engineers can provide you with full-process professional support from product selection, solution design, factory visits to delivery and maintenance.
The global pioneer of atmospheric pressure sealed nature air insulated technology.
contatc us
About us
Resource