circuit-breaker unit(B)
This ASNA circuit breaker unit (Symbol: B) adopts natural air insulation. It is composed of an atmospheric-pressure sealed tank fitted with a circuit breaker and a three-position disconnector (closed / open / earthed), as well as a cable compartment. It is capable of switching load currents of distribution circuits and interrupting short-circuit fault currents, and features isolation and maintenance earthing functions.
circuit-breaker unit(B)
The ASNA circuit breaker unit(symbol B)is insulated by nature-air and consists of a atmospheric pressure sealed tank with a circuit breaker, a disconnector (close / open / earth),and a cable room. It can achieve the switching of load current on distribution lines, the breaking of short-circuit faults, and has the functions of isolation and maintenance grounding.
The atmospheric pressure sealed tank, with equal pressure of inside and outside, no need to monitor pressure, no risk of gas leakage, and no maintenance required. There is a solution of one bay, two bays common tank, and three bays common tank.
Core functions
Protecr Function
Incoming/outgoing feeder circuit: A relay protection device integrated with three-stage overcurrent protection, zero-sequence protection and
Transformer outgoing feeder circuit: Self-powered relay protection devices are recommended. Powered by current transformers (CTs), they require no external operating power and satisfy short-circuit and overload protection requirements for distribution transformers.
The type of relay protection device can be selected in accordance with actual project conditions.
Operating Function
The circuit breaker is fitted with an electric operating mechanism capable of both manual and motorised energy storage. It can be equipped with one closing coil as well as one or two tripping coils.
Tripping coils are available in three types: conventional tripping coils, low-consumption coils (for use with self-powered relay protection devices), and coils with undervoltage trip function. The standard operating voltage is DC 48 V; custom options including AC 230 V, DC 110 V and DC 24 V are available.
The three-position switch is equipped with a manual operating mechanism, while a motorised three-position operating mechanism is supplied as an optional component.
The circuit breaker switchgear can be fitted with sensors for temperature, humidity, smoke detection, water immersion and video surveillance. Data from these sensors is uploaded to the SCADA system to enable real-time monitoring of the switchgear operating conditions. This allows potential risks to be eliminated at the early stage and guarantees reliable power supply of the circuit.
Multiple ASNA circuit breaker switchgears can be configured into a ring main power supply architecture. Leveraging the circuit breaker’s capability of fast fault interruption, the units can be interconnected to build a self-healing distribution network. Upon fault occurrence, faulty sections are automatically isolated, while power supply to fault-free sections is rapidly restored. This drastically cuts power outage duration and improves the overall power supply reliability of the distribution grid.
Parameter List
| Name | Unit | Parameter | |||||
| Rated voltage(Ur) | kV | 24 | |||||
| Rated frequency(fr) | Hz | 50 | |||||
| Rated current(lr) | A | 630 | 1250 | ||||
| Rated short-duration power-frequency withstand voltage(Ud) |
Common value | kV | 50 | ||||
| Across theisolating distance | 60 | ||||||
| Rated lightning impulse withstand voltage(up) | Common value | kV | 125 | ||||
| Across theisolating distance | 145 | ||||||
| Rated short-time withstand current(lk) | kA | 20 | 25 | ||||
| Rated short-time duration(tk) | s | 4 | |||||
| Rated peak withstand current(lp) | kA | 50 | 63 | ||||
| Rated short-circuit breaking current(lsc) | kA | 20 | 25 | ||||
| Rated short-circuit making current(lma) | Circuit breaker | kA | 50 | 63 | |||
| Three-positon disconnecter | |||||||
| Mechanical endurance | Circuit-breaker | time | 10000 | ||||
| Three-positon disconnecter | time | 3000 | |||||
| Electrical endurance | Circuit-breaker | class | E2 | ||||
| Earthing Switch | class | E2 | |||||
| Degree of protection by enclosure | IP4X | ||||||
| Degree of protection by Fully Sealed tank | IP65 | ||||||
| Dimension Low voltage chamber not included |
B | One bay | W(mm) | 550 | 600 | ||
| BB | Two bays common tank | 1030 | —— | ||||
| BBB | Three bays common tank | 1510 | —— | ||||
| —— | —— | D(mm) | 850 | ||||
| —— | —— | H(mm) | 1890,17001) | 1940 | |||
1) 1700mm is the solution for the low cable room of the B unit.
| Name | Unit | Parameter | ||||
| Rated voltage(Ur) | kV | 12 | ||||
| Rated frequency(fr) | Hz | 50 | ||||
| Rated continuous current(lr) | A | 630 | 1250 | |||
|
Rated short-duration power-frequency withstand voltage(Ud) |
Common value | kV | 28 | |||
| Across the isolating distance | 32 | |||||
| Rated lightning impulse withstand voltage(up) | Common value | kV | 75 | |||
| Across the isolating distance | 85 | |||||
| Rated short-time withstand current(Ik) | kA | 20 /25 | 20/25/31.5 | |||
| Rated short-time of short-circuit(tk) | s | 4 | ||||
| Rated peak withstand current(Ip) | kA | 50 / 63 | 50/63/80 | |||
| Rated short-circuit breaking current(Isc) | kA | 20 / 25 | 20/25/31.5 | |||
| Rated short-circuit making current(Ima) | Circuit breaker | kA | 50 / 63 | 50/63/80 | ||
| Three-positon disconnecter | ||||||
| Mechanical endurance | Circuit breaker | time | 10000 | |||
| Three-positon disconnecter | time | 3000 | ||||
| Electrical endurance | Circuit-breaker | class | E2 | |||
| Earthing Switch | class | E2 | ||||
| Degree of protection by enclosure | IP 4X | |||||
| Degree of protection by fully sealed tank | IP 65 | |||||
| Dimensions Low voltage chamber not included |
B | One bay | W(mm) | 460 | 550 | |
| BB | Two bays common tank | 810 | _ | |||
| BBB | Three bays common tank | 1160 | _ | |||
| — | —— | D(mm) | 800/900 | 900 | ||
| — | —— | H(mm) | 1640/1810 | 1810 | ||
Structure Of The Circuit Breaker Switchgear
Closing Knob
Opening Knob
Circuit - Breaker Operating Mechanism
Vacuum Circuit - Breaker
Interlock Push Pedal
Disconnector Operation Hole
Earthing Operation Hole
3 - position Disconnector / Earthing Operating Mechanism
3 - position Disconnector / Earthing Switch
Observation Window
Cable Room
Pressure Balance Device
Voltage Presence Indicating System