busbar section coupling unit
Core functions
Improved Power Supply Reliability
A single busbar can be split into two separate busbar sections. The two sections remain interconnected under normal operating conditions. In the event of a fault, the connection can be opened to confine the fault to only one busbar section and minimize the scope of power outages.
Coordination with Two Incoming Feeder Units for Automatic Bus Transfer
The two incoming feeder units are connected to Busbar Section I and Busbar Section II respectively, with the busbar section coupling cabinet serving as the tie. If power loss occurs on one incoming feeder, the busbar section coupling cabinet will close, and all loads will be supplied by the other power source.
Parameter List
| Name | Unit | Parameter | |
| Rated voltage(Ur) | kV | 24 | |
| Rated frequency(fr) | Hz | 50 | |
| Rated continuous current(lr) | A | 630 | |
| Rated short-duration power-frequency withstand voltage(Ud) | Common value | kV | 50 |
| Across the isolating distance | 60 | ||
| Rated lightning impulse withstand voltage(Up) | Common value | kV | 125 |
| Across the isolating distance | 145 | ||
| Rated short-time withstand current(Ik) | kA | 20 | |
| Rated short-time of short-circuit(tk) | s | 4 | |
| Rated peak withstand current(Ip) | kA | 50 | |
| Rated short-circuit breaking current(Isc) | kA | 20 | |
| Rated short-circuit making current(Ima) | Three-position disconnector | kA | 50 |
| Mechanical endurance | Circuit breaker | time | 10000 |
| Three-position disconnector | time | 3000 | |
| Degree of protection by enclosure | IP 4X | ||
| Degree of protection by fully sealed tank | IP 65 | ||
| Dimensions Low voltage chamber not included | W(mm) | 1030 | |
| D(mm) | 850 | ||
| H(mm) | 1890 | ||
| Name | Unit | Parameter | |
| Rated voltage(Ur) | kV | 12 | |
| Rated frequency(fr) | Hz | 50 | |
| Rated continuous current(lr) | A | 630 | |
| Rated short-duration power-frequency withstand voltage(Ud) | Common value | kV | 28 |
| Across the isolating distance | 32 | ||
| Rated lightning impulse withstand voltage(Up) | Common value | kV | 75 |
| Across the isolating distance | 85 | ||
| Rated short-time withstand current(Ik) | kA | 20 /25 | |
| Rated short-time of short-circuit(tk) | s | 4 | |
| Rated peak withstand current(Ip) | kA | 50 / 63 | |
| Rated short-circuit breaking current(Isc) | kA | 20 / 25 | |
| Rated short-circuit making current(Ima) | Three-position disconnector | kA | 50 / 63 |
| Mechanical endurance | Circuit breaker | time | 10000 |
| Three-position disconnector | time | 3000 | |
| Degree of protection by enclosure | IP 4X | ||
| Degree of protection by fully sealed tank | IP 65 | ||
| Dimensions Low voltage chamber not included |
W(mm) | 810 | |
| D(mm) | 800 | ||
| H(mm) | 1640 | ||
Application
Questions and answered
Let's get in touch!
No matter which stage your project is at, our professional team of engineers can provide you with full-process professional support from product selection, solution design, factory visits to delivery and maintenance.