12kV 1250A Atmospheric pressure sealed nature-air insulated switchgear/RMU, with a current of 1250A, can carry more loads and meet the demands of future green and smart distribution networks. There is no SF6 or synthetic gas. Only nature air is used for insulation, Comply with the F-Gas regulation (EU) 2024/573
HMpower is made with the progressive technology and quality assured materials.
What is ASNA RMU?
ASNA means:Atmospheric pressure Sealed Nature-Air insulated RMU
ASNA is a brand new type of RMU that uses nature-air as the main insulation medium.
Its main electrical circuits are sealed within an Atmospheric pressure sealed cabinet that maintains the same pressure as the surrounding environment and is equipped with filtration and pressure balance functions.
During its entire life cycle, there is no risk of air leakage, no need for pressure monitoring, and it can prevent dust, solid particles, salt fog particles, etc. from entering the sealed cabinet .
Air-insulated, greenhouse gases free, Comply with the F-Gas regulation (EU) 2024/573.
The sealed cabinet is sealed under atmospheric pressure, avoiding the risk of insulation performance decline due to pressure leakage.
The current is 1250A, which can carry more loads.
The operating mechanism is stable, and the mechanical life can reach 10,000 times.
Single-phase insulation technology eliminate sudden short-circuit faults between phases.
Name |
Unit |
Smart Ring |
|||
Rated voltage(Ur) |
kV |
12 |
|||
Rated frequency(fr) |
Hz |
50 |
|||
Rated continuous current(Ir) |
A |
1250 |
630 |
||
Rated short-duration power-frequency withstand voltage(Ud) |
Common value |
kV |
28 |
||
Across the isolating distance |
32 |
||||
Rated lightning impulse withstand voltage(Up) |
Common value |
kV |
75 |
||
Across the isolating distance |
85 |
||||
Rated short-time withstand current(Ik) |
kA |
31.5 / 25 |
20 / 25 |
||
Rated short-time of short-circuit(tk) |
s |
4 |
|||
Rated peak withstand current(Ip) |
kA |
80 / 63 |
50 / 63 |
||
Rated short-circuit breaking current(Isc) |
kA |
31.5 / 25 |
20 / 25 |
||
Rated short-circuit making current(Ima) |
Vacuum interrupter |
kA |
80 / 63 |
50 / 63 |
|
Earth Switch | |||||
Mechanical endurance |
Circuit-breaker |
time |
10000 |
||
Isolator |
time |
3000 |
|||
Earthing Switch |
time |
3000 |
|||
Electrical endurance |
Circuit-breaker |
class |
E2 |
||
Earthing Switch |
class |
E2 |
|||
Degree of protection by enclosure |
|
IP 4X |
|||
Degree of protection by fully sealed tank |
|
IP 65 |
|||
|
Low voltage chamber not included |
B |
Circuit-breaker unit |
W(mm) |
550 |
460 |
PTB |
CB unit with PT |
750 |
-- |
||
D |
Cable connection unit |
450~550 |
-- |
||
PT |
Busbar PT unit |
600 |
-- |
||
BS |
Busbar Sectionliser unit |
1000 |
-- |
||
-- |
-- |
D(mm) |
900 |
||
-- |
-- |
H(mm) |
1810 |
||