What is the minimum height of the 24 kV switchgear, and what impact does this height have on CT and PT installation?
Excluding the secondary top compartment, the minimum height of the 24 kV switchgear is 1700 mm. This height imposes considerable constraints on the installation of CTs and busbar PTs. It is recommended to select 1 A for the CT secondary current. Please consult us for detailed accuracy class and burden parameters. If busbar PTs are adopted, please consult us on the installation arrangement.